HSKG 300/M16/B/B BG

Art.-Nr. 17027.2

High-power stud terminal, Stud connection, Mounting type: Mounting rail TS 35/7.5, Rated cross-section: 300 mm², Width: 55 mm, Colour: Beige

Download datasheet

Details

Commercial data

General

Colour
Beige
Country of origin
DE
Customs number
85369010
GTIN (EAN)
4044211177447
Packaging unit
5
Product description
High-power stud terminal
Quantity unit
PC
Unit of weight
G
Weight per piece (including packaging)
529 g
Weight per piece (not including packaging)
510 g
Technical data

Dimensions

Height TS 35/7.5
86 mm
Height TS 35/7.5 with TW/ADH
90 mm
Length
164 mm
Length with TW/ADH
288 mm
Width
55 mm

Ratings

Contamination degree
3
Maximum power dissipation for nominal condition
16.64 W
Overvoltage category
III
Rated cross-section
300 mm²
Rated current
520 A
Rated impulse voltage
8 kV
Rated voltage
1000 V

Connection data

Bolt head
Hexagon
Bolt thread
M 16
Connection position
Top
Connection principle
Stud connection
Connections
2
Contact wire range
≤ 300 mm²
Number of levels
1
Number of terminals per level
2
Tightening torque, max.
60 Nm
Tightening torque, min.
25 Nm
Wire cross-section AWG, max.
600 Kcmil
Wire cross-section AWG, min.
6

Further technical data

DIN 46234 / 1 cable lug per side, max.
240 mm²
DIN 46234 / 1 cable lug per side, min.
25 mm²
DIN 46234 / 2 cable lugs per side, max.
240 mm²
DIN 46234 / 2 cable lugs per side, min.
50 mm²
DIN 46235: 1 cable lug per side, max.
300 mm²
DIN 46235: 1 cable lug per side, min.
50 mm²
DIN 46235: 2 cable lugs per side, max.
240 mm²
DIN 46235: 2 cable lugs per side, min.
50 mm²
Mounting type
Mounting rail TS 35/7,5
Number of cross-connection channels
2
Spanner width (AF)
24 mm

Materials

Fire load
3,642 MJ
Flammability class UL 94
V-0
Insulation housing
Polyamide 6.6
Working temperature, max.
120 °C
Working temperature, min.
-40 °C
Authorisations

Standards and regulations

Bureau Veritas approval
IEC 60947-7-1
Bureau Veritas approval granted
EAC approval
TR ZU 004/2011
EAC approval granted

cUL Recognized

E95701
cUL Recognized
1
cUL Usegroup B: rated current
510 A
cUL Usegroup B: rated voltage
1000 V
cUL Usegroup C: rated current
510 A
cUL Usegroup C: rated voltage
1000 V
cUL approval
C22.2 No 158
cUL torque, max.
60 Nm
cUL torque, min.
25 Nm
cUL wire cross-section AWG, max.
600 Kcmil
cUL wire cross-section AWG, min.
6
cUL wire material
Cu

KEMA KEUR approval

KEMA KEUR approval
EN 60947-7-1:2009
KEMA KEUR approval granted
KEMA rated current
520 A
KEMA rated impulse voltage
8 kV
KEMA rated voltage
1000 V
KEMA torque, max.
60 Nm
KEMA torque, min.
25 Nm
KEMA wire cross-section, max.
300 mm²

UL Recognized

UL File Number
E95701
UL Recognized
1
UL Usegroup B: rated current (only for factory wiring)
420 (510) A
UL Usegroup B: rated voltage
1000 V
UL Usegroup C: rated current (only for factory wiring)
420 (510) A
UL Usegroup C: rated voltage
1000 V
UL approval
UL 1059
UL factory wiring
UL field wiring
UL torque, max.
531 Lb In.
UL torque, min.
221.3 Lb In.
UL wire cross-section AWG, max.
600 Kcmil
UL wire cross-section AWG, min.
6
UL wire material
Cu

German Lloyd approval

DNV GL Certificate number
TAE00002JH
DNV GL Location Classes
Temperature: B, Humidity: B, Vibration: A
DNV GL approval granted
1
DNV GL rated cross-section
300 mm²
DNV GL rated current
520 A
DNV GL rated impulse voltage
8 kV
DNV GL rated voltage
1000 V
DNV GL test standard
IEC 60947-7-1:2009
Environment

Environmental Product Compliance

EU-POP Conform
PROP 65 Conform
REACH Candidate Substance Note
𐄂
REACH Conform
REACH Reference date
2026-02-04
RoHS Conform
TSCA Conform
Download
File
Type
Size
Filetime

Accessories

Results
Protective hood
End stop
Quick marking
Partition plate