SDK 4/2A GR
Art.-Nr. 17380.6
Feed-through terminal, Screw connection, Mounting type: Mounting surface, Rated cross-section: 4 mm², Colour: Grey
Download datasheetDetails
Commercial data
General
- Colour
- Grey
- Country of origin
- CZ
- Customs number
- 85369010
- Packaging unit
- 50
- Product description
- Panel feed-through terminal
- Quantity unit
- PC
- Unit of weight
- G
- Weight per piece (including packaging)
- 13.94 g
- Weight per piece (not including packaging)
- 13.91 g
Technical data
Dimensions
- Height of inner part
- 26.8 mm
- Height of outer part
- 28.2 mm
- Length of inner part
- 22.4 mm
- Length of outer part
- 27.5 mm
- Width of inner part
- 8.1 mm
- Width of outer part
- 8.1 mm
Ratings
- Contamination degree
- 3
- Current load, max.
- 41 A
- Maximum power dissipation for nominal condition
- 1.02 W
- Overvoltage category
- III
- Rated cross-section
- 4 mm²
- Rated current
- 32 A
- Rated impulse voltage
- 6 kV
- Rated voltage
- 630 V
- Rated voltage when using spacer plates and adapter plates, and when mounting on a conductive housing panel
- 1000 V
- Rated voltage when using spacer plates and mounted on a conductive housing panel
- 800 V
Connection data
- Connection principle
- Screw connection
- No. of poles
- 1
- Number of terminals per pole
- 2
- Screw head
- Slotted
- Screw threading
- M 3
- Stripping length
- 10 mm
- Tightening torque, max.
- 1 Nm
- Tightening torque, min.
- 0.5 Nm
- Wire cross-section AWG, max.
- 10
- Wire cross-section AWG, min.
- 26
- Wire cross-section single core (rigid)/stranded, max.
- 6 mm²
- Wire cross-section single-core (rigid) / stranded, min.
- 0.2 mm²
- Wire cross-section stranded with wire-end ferrules, max.
- 4 mm²
- Wire cross-section stranded with wire-end ferrules, min.
- 0.2 mm²
- Wire cross-section stranded, max.
- 6 mm²
- Wire cross-section stranded, min.
- 0.2 mm²
Further technical data
- Gauge plug acc. to EN 60 947-1
- A4
- Mounting type
- Mounting face
- Sheet thickness max.
- 4 mm
- Sheet thickness min.
- 1 mm
- Sheet thickness when using spacer plates, max.
- 3 mm
- Sheet thickness when using spacer plates, min.
- 1 mm
- Thickness of mounting plate, max.
- 4
- Thickness of mounting plate, min.
- 1
Materials
- Flammability class UL 94
- V-0
- Insulation housing
- Polyamide 6.6
- Working temperature, max.
- 120 °C
- Working temperature, min.
- -40 °C
Authorisations
Standards and regulations
- EAC approval
- TR ZU 004/2011
- EAC approval granted
cUL Recognized
- E95701
- cUL Recognized
- 1
- cUL Usegroup B: rated current
- 30 A
- cUL Usegroup B: rated current when using the SDK ...-VPI moulded plate and the SDK ...-TWI partition
- 30 A
- cUL Usegroup B: rated current when using the SDK 4-DP spacer plate and the SDK 4-AP adapter plate
- 30 A
- cUL Usegroup B: rated voltage
- 300 V
- cUL Usegroup B: rated voltage when using the SDK ...-VPI moulded plate and the SDK ...-TWI partition
- 600 V
- cUL Usegroup B: rated voltage when using the SDK 4-DP spacer plate and the SDK 4-AP adapter plate
- 300 V
- cUL Usegroup C: rated current when using the SDK 4-DP spacer plate and the SDK 4-AP adapter plate
- 30 A
- cUL Usegroup C: rated current when using the SDK 4-VPI moulded plate or the SDK 4-TWI partition
- 30 A
- cUL Usegroup C: rated voltage when using the SDK 4-DP spacer plate and the SDK 4-AP adapter plate
- 300 V
- cUL Usegroup C: rated voltage when using the SDK 4-VPI moulded plate or the SDK 4-TWI partition
- 600 V
- cUL Usegroup D: rated current
- 30 A
- cUL Usegroup D: rated current when using the SDK ...-DP spacer plate and the SDK ...-AP adapter plate
- 30 A
- cUL Usegroup D: rated current when using the SDK 4-DP spacer plate
- 5 A
- cUL Usegroup D: rated voltage
- 300 V
- cUL Usegroup D: rated voltage when using the SDK ...-DP spacer plate and the SDK ...-AP adapter plate
- 300 V
- cUL Usegroup D: rated voltage when using the SDK 4-DP spacer plate
- 600 V
- cUL approval
- C22.2 No 158
- cUL torque, max.
- 1 Nm
- cUL torque, min.
- 0.5 Nm
- cUL wire cross-section single-core (rigid) AWG, max.
- 10
- cUL wire cross-section single-core (rigid) AWG, min.
- 26
- cUL wire cross-section stranded AWG, max.
- 10
- cUL wire cross-section stranded AWG, min.
- 26
- cUL wire material
- Cu
KEMA KEUR approval
- KEMA KEUR approval
- EN 60947-7-1:2009
- KEMA KEUR approval granted
- KEMA conventional thermal current in free air
- 41 A
- KEMA rated current
- 32 A
- KEMA rated impulse voltage (for 250 V without partitions)
- 6 kV
- KEMA rated voltage
- 630 V
- KEMA rated voltage when using spacer plates and adapter plates, and when mounting on a conductive housing panel
- 1000 V
- KEMA rated voltage when using spacer plates and mounted on a conductive housing panel
- 800 V
- KEMA wire cross-section, max.
- 6 mm²
- KEMA wire cross-section, min.
- 0.2 mm²
UL Recognized
- UL File Number
- E95701
- UL Recognized
- 1
- UL Usegroup B: rated current
- 30 A
- UL Usegroup B: rated current when using the SDK ...-DP spacer plate
- 30 A
- UL Usegroup B: rated current when using the SDK 4-DP spacer plate and the SDK 4-AP adapter plate
- 600 A
- UL Usegroup B: rated voltage
- 300 V
- UL Usegroup B: rated voltage when using the SDK ...-DP spacer plate
- 300 V
- UL Usegroup B: rated voltage when using the SDK 4-DP spacer plate and the SDK 4-AP adapter plate
- 30 V
- UL Usegroup C: rated current when using the SDK 4-DP spacer plate
- 30 A
- UL Usegroup C: rated current when using the SDK 4-DP spacer plate and the SDK 4-AP adapter plate
- 30 A
- UL Usegroup C: rated voltage when using the SDK 4-DP spacer plate
- 300 V
- UL Usegroup C: rated voltage when using the SDK 4-DP spacer plate and the SDK 4-AP adapter plate
- 600 V
- UL Usegroup D: rated current
- 30 A
- UL Usegroup D: rated current when using the SDK 4-VPI moulded plate or the SDK 4-TWI partition
- 5 A
- UL Usegroup D: rated voltage
- 300 V
- UL Usegroup D: rated voltage when using the SDK 4-VPI moulded plate or the SDK 4-TWI partition
- 600 V
- UL approval
- UL 1059
- UL factory wiring
- UL field wiring
- UL torque, max.
- 8.85 Lb In.
- UL torque, min.
- 4.42 Lb In.
- UL wire cross-section single-core (rigid) AWG, max.
- 10
- UL wire cross-section single-core (rigid) AWG, min.
- 26
- UL wire cross-section stranded AWG, max.
- 10
- UL wire cross-section stranded AWG, min.
- 26
- UL wire material
- Cu
Environment
Environmental Product Compliance
- REACH Candidate Substance Note
- 𐄂
- REACH Conform
- ✓
- REACH Reference date
- 2024-06-27
- RoHS Conform
- ✓
Download
File
Type
Size
Filetime
Accessories
Results
Outer 6-pole adapter plate
Set 23.05.2017, spacer plate inside + outside
Set: outer flange plate
Quick marking
You have agreed to the storage of data Customize
Important notice
For your own safety, please switch to an up-to-date browser in order to be able to make full use of our services.
Your web browser is outdated and contains open security vulnerabilities
To ensure the security of your data, some functions on our website may not be accessible with your browser.
For your own safety, please switch to an up-to-date browser in order to be able to make full use of our services.
Microsoft Edge
Successor to Internet Explorer
Google Chrome
Mozilla Firefox