SIK 10/Z BG

Art.-Nr. 1102.2

Fuse-disconnect terminal, Screw connection, Mounting type:Mounting rail TS 35/7.5 and TS 32, Rated cross-section: 10 mm², Width: 10 mm, Colour: Beige

Download datasheet

Details

Commercial data

General

Colour
Beige
Country of origin
BG
Customs number
85369010
GTIN (EAN)
4044211016395
Packaging unit
25
Product description
Fuse-disconnect terminal
Quantity unit
PC
Unit of weight
G
Weight per piece (including packaging)
28.68 g
Weight per piece (not including packaging)
26 g
Technical data

Dimensions

Height TS 32
69 mm
Height TS 35/7.5
73 mm
Length
60 mm
Width
10 mm

Ratings

Contamination degree
3
Overvoltage category
III
Rated cross-section
10 mm²
Rated current (as fuse-disconnect terminal)
10 A
Rated impulse voltage
8 kV
Rated voltage (determined by the illuminated display and fuse being used)
500 V

Connection data

Connection position
Lateral
Connection principle
Screw connection
Connections
2 / extraction lever
Number of levels
1
Number of terminals per level
2
Screw head
Slotted
Screw threading
M 4
Stripping length
12 mm
Tightening torque, max.
2 Nm
Tightening torque, min.
1.2 Nm
Wire cross-section AWG, max.
8
Wire cross-section AWG, min.
22
Wire cross-section single core (rigid)/stranded, max.
10 mm²
Wire cross-section single-core (rigid) / stranded, min.
0.2 mm²
Wire cross-section stranded with wire-end ferrules, max.
10 mm²
Wire cross-section stranded with wire-end ferrules, min.
0.2 mm²
Wire cross-section stranded, max.
10 mm²
Wire cross-section stranded, min.
0.2 mm²

Further technical data

Fuse size
6,3 x 25 / 6,3 x 32 mm
Gauge plug acc. to EN 60 947-1
A5
Mounting type
Mounting rail TS 35/7.5 and TS 32
Power loss in compound arrangement - only short-circuit protection, max.
2,5 / 2,5 W / A
Power loss in compound arrangement - overload and short-circuit protection, max.
2,5 / 2,5 W / A
Power loss in singular arrangement - only short-circuit protection, max.
4 / 10 W / A
Power loss in singular arrangement - overload and short-circuit protection, max.
2,5 / 2,5 W / A
Version of fuse cartridge
G fuse 6.3 x 25 / 6.3 x 32
Version of fuse holder
Swivelling
Voltage fuse
250 V

Materials

Flammability class UL 94
V-2
Insulation housing
Polyamide 6.6
Working temperature, max.
105 °C
Working temperature, min.
-40 °C
Authorisations

Standards and regulations

EAC approval
TR ZU 004/2011
EAC approval granted
Nemko approval
EN 60947-7-3:2002
Nemko approval granted

cUL Recognized

cUL Recognized
1
cUL Usegroup B: rated current
16 A
cUL Usegroup B: rated voltage
600 V
cUL Usegroup C: rated current
16 A
cUL Usegroup C: rated voltage
600 V
cUL approval
C22.2 No 158
cUL torque
16 Nm
cUL wire cross-section single-core (rigid) AWG, max.
12
cUL wire cross-section single-core (rigid) AWG, min.
22
cUL wire cross-section stranded AWG, max.
12
cUL wire cross-section stranded AWG, min.
22
cUL wire material
Cu

KEMA KEUR approval

KEMA KEUR approval
EN 60947-7-3:2009
KEMA KEUR approval granted
KEMA fuse size
6,3 x 25 / 6,3 x 32 mm
KEMA power loss in compound arrangement - only short-circuit protection, max.
2,5 / 2,5 W / A
KEMA power loss in compound arrangement - overload and short-circuit protection, max.
2,5 / 2,5 W / A
KEMA power loss in singular arrangement - only short-circuit protection, max.
4 / 10 W / A
KEMA power loss in singular arrangement - overload and short-circuit protection, max.
2,5 / 2,5 W / A
KEMA rated current
10 A
KEMA rated impulse voltage
8 kV
KEMA rated voltage
500 V
KEMA torque, max.
2 Nm
KEMA torque, min.
1.2 Nm
KEMA voltage fuse, max.
250 V
KEMA wire cross-section single core (rigid), min.
0.2 mm²
KEMA wire cross-section single-core (rigid), max.
10 mm²
KEMA wire cross-section stranded, max.
10 mm²
KEMA wire cross-section stranded, min.
0.2 mm²

UL Recognized

UL Recognized
1
UL Usegroup B: rated current
16 A
UL Usegroup B: rated voltage
600 V
UL Usegroup C: rated current
16 A
UL Usegroup C: rated voltage
600 V
UL approval
UL 1059
UL factory wiring
UL field wiring
UL torque
16 Lb In
UL wire cross-section single-core (rigid) AWG, max.
12
UL wire cross-section single-core (rigid) AWG, min.
22
UL wire cross-section stranded AWG, max.
12
UL wire cross-section stranded AWG, min.
22
UL wire material
Cu

German Lloyd approval

DNV GL Certificate number
TAE00002JJ
DNV GL Location Classes
Temperature: B, Humidity: B, Vibration: A
DNV GL approval granted
1
DNV GL rated cross-section
10 mm²
DNV GL rated current
10 A
DNV GL rated voltage
500 V
DNV GL test standard
IEC 60947-7-3:2002
Environment

Environmental Product Compliance

REACH Candidate Substance Note
𐄂
REACH Conform
REACH Reference date
2025-01-21
RoHS Conform
Download
File
Type
Size
Filetime